OmronConnectedCipMaster
Purpose
Omron Connected EtherNet/IP CIP Tag Read and Write Driver
Open the plugin
Enter "Development Configuration → Collection Configuration", create a device and select "OmronConnectedCipMaster" in "Collection Plugin".
Supported channels and data types
| Channel type | Pre-configuration check |
|---|---|
| TCP Client | Confirm network reachability of the device IP, port, and gateway to the device. |
Optional data types: Boolean, Byte, Int16, UInt16, Int32, UInt32, Int64, UInt64, Float, Double, String, Decimal
Plugin properties
Protocol parameters
| Setting | Description |
|---|---|
| Target slot | Default: 0; fill in: text input. Set the slot number where the PLC CPU module is located. |
| Backplane port | Default: 1; fill in: text input. Set up a controller backplane port or path segment. |
Running parameters
| Setting | Description |
|---|---|
| Connection timeout ratio | Default: 2; fill in: text input. Connection timeout multiplier; used for large Forward Open requests, the default value is 2 |
Address rules
- Tag Name
- Omron connected CIP tags; array local access uses Tag[index].
Functions
| Function | Purpose |
|---|---|
| Read and write | Read a confirmed point and write only to an approved test point. |
| Messages | View sent and received frames, protocol fields, and error details. |
Device debug
Enter "Development Configuration → Collection Configuration", select the current device and click "More Functions", then open "Debug".
Dedicated debugging page
Open Development Configuration → Collection Configuration, select the device, and open More Functions → Debug. The following image shows the plugin-specific debug page.


Verify the configuration
Use a confirmed on-site address to perform reading. The return value, data type and byte order should be consistent with the point list; after the writable point is written, it should be read back according to on-site requirements.
Troubleshooting
- Address reading failed: Check the station number, register or node ID one by one according to the address rules on this page, and confirm that the data type is consistent with the device point list.
Related links
- Collection configuration: View channel, device and common variable configuration.
- Plugin Index: Find other collection or data-forward plugins.