Fuji SPB master

Fuji SPB protocol PLC address read and write driver

Open the plugin

Enter “Development Configuration → Collection Configuration”, create a device and select “FujiSpbMaster” in “Collection Plugin”.

Supported channels and data types

Channel typePre-configuration check
Serial PortConfirm that the serial port is not occupied by other programs and maintains the same baud rate, data bits, stop bits and parity bits as the device.
TCP ClientConfirm network reachability of the device IP, port, and gateway to the device.
TCP serverConfirm that the local listening address and port are available, and allow on-site devices to actively connect to the gateway.

Optional data types: Boolean, Int16, UInt16, Int32, UInt32, Float, String

This list describes types allowed by the plugin editor. Address width, arrays, string length and read/write restrictions still follow this page; it does not mean that every address supports every type.

Plugin properties

Protocol parameters

SettingDescription
PLC station numberDefault: 1; fill in: text input. PLC station number; SPB requests to use two-digit uppercase hexadecimal station number

Address rules

  • Fuji SPB WORD address: Y, X, M, L, TC, CC, TN, CN, D, R, W, such as D100, TN20.
  • Boolean address can use WORD address and bit number, such as D10.12; X, Y, M, L, TC, CC can also directly use continuous bit number, such as M35.
  • Single read 1 to 105 WORD, single write 1 to 103 WORD; Boolean write only writes one bit at a time.
  • PLC communication parameters must be configured without BCC and CRLF end code enabled.

Device debug

Enter “Development Configuration → Collection Configuration”, select the current device then open “Protocol Debug” at the top of the workspace.

FujiSpbMaster: Read/Write

FujiSpbMaster: Messages

Functions

FunctionPurpose
Read and writeRead a confirmed point and write only to an approved test point.
MessagesView sent and received frames, protocol fields, and error details.

Verify the configuration

Monitor D100 online in the PLC engineering tool, compare its value with the gateway variable and confirm advancing sample times.

Troubleshooting

  • For response parsing failures, check BCC and CRLF first; reads allow 105 WORDs and writes 103.
  • The serial port device does not respond: Confirm that the serial port is not occupied, and check the baud rate, data bits, stop bits and parity bits.