TOYOPUC master

Toyo PUC computer link address read and write, status and command driver

Open the plugin

Enter “Development Configuration → Collection Configuration”, create a device and select “ToyoPucMaster” in “Collection Plugin”.

Supported channels and data types

Channel typePre-configuration check
TCP ClientConfirm network reachability of the device IP, port, and gateway to the device.

Optional data types: Boolean, Int16, UInt16, Int32, UInt32, Int64, UInt64, Float, Double, String

This list describes types allowed by the plugin editor. Address width, arrays, string length and read/write restrictions still follow this page; it does not mean that every address supports every type.

Address rules

  • Toyo PUC address values ​​use hexadecimal. The current program area WORD supports K, V, T, C, L, X, Y, M, S, N, R, D, and B.
  • Program area WORD supports EK, EV, ET, EC, EL, EX, EY, EM, ES, EN, EB, H, U, GX, GY, GM; prg=0..255 can be configured explicitly in the basic area.
  • Boolean only supports K, V, T, C, L, X, Y, M and the corresponding extended relay area, and must use WORD. bits, such as M10.A.
  • The current program area K/V/T/C/L/X/Y/M supports native single-point writing; multi-point or program area writing does not perform read, modify, and write, and is directly rejected.
  • The current version only supports establishing TCP client sessions via the 2PORT-EFR module.

Special methods

MethodPurposeParameters
ReadRandomWordsAsyncRandomly read WORDaddresses=D0,D10,M20

Device debug

Enter “Development Configuration → Collection Configuration”, select the current device then open “Protocol Debug” at the top of the workspace.

Dedicated debugging page

The protocol debug page is used to read Toyo PUC random word data.

ToyoPucMaster: Operations

Debugging notes

Enter a random word address list to read WORD. The current dedicated page only provides query operations.

Functions

FunctionPurpose
Random WORD readUse Random WORD read to inspect mapped values, status, counters, recent messages, or the latest result.
Debug resultView the returned value, success state, or error message.

Verify the configuration

Monitor D100 online in the PLC engineering tool, compare its value with the gateway variable and confirm advancing sample times.

Writes and control operations require an approved test point and the site safety procedure.

Troubleshooting

  • Device numbers are hexadecimal; M10.A selects a bit. Multi-point bit writes are unsupported; Modbus decimal addressing does not apply.
  • Special method execution fails: Check method parameters and permissions; control, write or reset methods also need to confirm that the device is in a state that allows operation.