Omron Connected EtherNet/IP CIP Tag Read and Write Driver

Open the plugin

Enter “Development Configuration → Collection Configuration”, create a device and select “OmronConnectedCipMaster” in “Collection Plugin”.

Supported channels and data types

Channel typePre-configuration check
TCP ClientConfirm network reachability of the device IP, port, and gateway to the device.

Optional data types: Boolean, Byte, Int16, UInt16, Int32, UInt32, Int64, UInt64, Float, Double, String, Decimal

This list describes types allowed by the plugin editor. Address width, arrays, string length and read/write restrictions still follow this page; it does not mean that every address supports every type.

Plugin properties

Protocol parameters

SettingDescription
Target slotDefault: 0; fill in: text input. Set the slot number where the PLC CPU module is located.
Backplane portDefault: 1; fill in: text input. Set up a controller backplane port or path segment.

Running parameters

SettingDescription
Connection timeout ratioDefault: 2; fill in: text input. Connection timeout multiplier; used for large Forward Open requests, the default value is 2

Address rules

  • Tag Name
  • Omron connected CIP tags; array local access uses Tag[index].

Device debug

Enter “Development Configuration → Collection Configuration”, select the current device then open “Protocol Debug” at the top of the workspace.

OmronConnectedCipMaster: Read/Write

OmronConnectedCipMaster: Messages

Functions

FunctionPurpose
Read and writeRead a confirmed point and write only to an approved test point.
MessagesView sent and received frames, protocol fields, and error details.

Verify the configuration

Monitor DemoValue online in the PLC engineering tool, compare its value with the gateway variable and confirm advancing sample times.

Troubleshooting

  • Confirm Forward Open before checking tag scope, case and type; a route does not replace the PLC IP.