Omron FINS master
Omron FINS TCP, UDP and serial address read and write drivers
Open the plugin
Enter “Development Configuration → Collection Configuration”, create a device and select “OmronFinsMaster” in “Collection Plugin”.
Supported channels and data types
| Channel type | Pre-configuration check |
|---|---|
| TCP Client | Confirm network reachability of the device IP, port, and gateway to the device. |
| UDP | Confirm the local binding address, port and firewall rules, and check the source of the packet. |
Optional data types: Boolean, Byte, Int16, UInt16, Int32, UInt32, Int64, UInt64, Float, Double, String, Decimal
This list describes types allowed by the plugin editor. Address width, arrays, string length and read/write restrictions still follow this page; it does not mean that every address supports every type.
Plugin properties
Protocol parameters
| Setting | Description |
|---|---|
| ICF | Default: 128; fill in: text input. Set the ICF used for protocol communication. |
| Network layer information | Default: 2; fill in: text input. Set the network layer information used for protocol communication. |
| DNA | Default: 0; fill in: text input. Sets the DNA used for protocol communication. |
| DA2 | Default: 0; fill in: text input. Set the DA2 used for protocol communication. |
| SNA | Default: 0; fill in: text input. Set the SNA used for protocol communication. |
| SA2 | Default: 0; fill in: text input. Set SA2 used for protocol communication. |
| SID | Default: 0; fill in: text input. Set the SID used for protocol communication. |
Address rules
| Memory area | Address example |
|---|---|
| DM Area | D0 |
| CIO Area | C0 |
| Work Area | W0 |
| Holding Bit Area | H0 |
| Auxiliary Bit Area | A0 |
| EM Area | E0.0 |
| Timer Area | TIM0 |
| Counter Area | CNT0 |
| Index Register | IR0 |
| Data Register | DR0 |
| Condition Flags | CF1.1 |
Device debug
Enter “Development Configuration → Collection Configuration”, select the current device then open “Protocol Debug” at the top of the workspace.


Functions
| Function | Purpose |
|---|---|
| Read and write | Read a confirmed point and write only to an approved test point. |
| Messages | View sent and received frames, protocol fields, and error details. |
Verify the configuration
Monitor D0 online in the PLC engineering tool, compare its value with the gateway variable and confirm advancing sample times.
Troubleshooting
- TCP and UDP use different transports. IP reachability does not validate FINS nodes/routes; changing only the port does not switch the protocol.
Related links
- Collection configuration: View channel, device and common variable configuration.
- Plugin Index: Find other collection or data-forward plugins.