Skip to Content
On this page

Inovance AM/H3U/H5U Modbus master

Inovance PLC Modbus and dedicated address model collection driver

Open the plugin

Enter “Development Configuration → Collection Configuration”, create a device and select “InovanceMaster” in “Collection Plugin”.

Supported channels and data types

Channel typePre-configuration check
Serial PortConfirm that the serial port is not occupied by other programs and maintains the same baud rate, data bits, stop bits and parity bits as the device.
TCP ClientConfirm network reachability of the device IP, port, and gateway to the device.
TCP serverConfirm that the local listening address and port are available, and allow on-site devices to actively connect to the gateway.

Optional data types: Boolean, Byte, Int16, UInt16, Int32, UInt32, Int64, UInt64, Float, Double, String, Decimal

This list describes types allowed by the plugin editor. Address width, arrays, string length and read/write restrictions still follow this page; it does not mean that every address supports every type.

Plugin properties

Protocol parameters

SettingDescription
Inovance TypeDefault: 0; fill in: drop-down selection. Set the Inovance type used for protocol communication.
Modbus typeDefault: ModbusTcp; fill in: drop-down selection. Set the Modbus type used for protocol communication.
Default station numberDefault: 1; fill in: text input. Set the default station number used when the station number is not specified separately in the variable address.

Request packing

SettingDescription
FC1 Maximum number of read coil bitsDefault: 1600; Range: 1~2000; Fill in: text input. Set the maximum number of FC1 read coil bits used for a single read or write or group packet.
FC2 Maximum number of read discrete input bitsDefault: 1600; Range: 1~2000; Fill in: text input. Set the maximum number of read discrete input bits used by FC2 for a single read or write or group packet.
FC3 Maximum number of read holding registersDefault: 100; Range: 1~125; Fill in: text input. Set the maximum number of FC3 read holding registers used for a single read or write or group package.
FC4 Maximum number of read input registersDefault: 100; Range: 1~125; Fill in: text input. Set the maximum number of FC4 read input registers used for a single read and write or group package.
FC15 Maximum number of coil bits written in batchesDefault: 1968; Range: 1~1968; Fill in: text input. Set the maximum number of FC15 batch write coil bits used for a single read or write or group packet.
FC16 Maximum number of batch write registersDefault: 123; Range: 1~123; Fill in: text input. Set the maximum number of FC16 batch write registers used for a single read or write or group package.

Connection configuration

SettingDescription
DTU IDFill in: text input. Sets the identifier used to identify the current device connection through the DTU service.

Address rules

  • AM series
  • Q0.0
  • IX0.0
  • MX0.0
  • MW0
  • MD0
  • MB0
  • SM0
  • SD0
  • s=2;SD0 supports additional specified station number
  • H3U
  • M0
  • SM0
  • S0
  • T0
  • C0
  • X0
  • Y0
  • D0
  • SD0
  • R0
  • s=2;SD0 supports additional specified station number
  • H5U
  • M0
  • B0
  • S0
  • X0
  • Y0
  • D0
  • R0
  • s=2;D0 supports additional specified station number

Device debug

Enter “Development Configuration → Collection Configuration”, select the current device then open “Protocol Debug” at the top of the workspace.

InovanceMaster: Read/Write

InovanceMaster: Messages

Functions

FunctionPurpose
Read and writeRead a confirmed point and write only to an approved test point.
MessagesView sent and received frames, protocol fields, and error details.

Verify the configuration

Monitor D0 online in the PLC engineering tool, compare its value with the gateway variable and confirm advancing sample times.

Troubleshooting

  • AM, H3U and H5U have different logical addresses; AM MW/MD cannot replace H3U D-area addresses.
  • The serial port device does not respond: Confirm that the serial port is not occupied, and check the baud rate, data bits, stop bits and parity bits.