Panasonic MC 3E Binary master

Panasonic QnA compatible MC 3E PLC address read and write driver

Open the plugin

Enter “Development Configuration → Collection Configuration”, create a device and select “PanasonicMcMaster” in “Collection Plugin”.

Supported channels and data types

Channel typePre-configuration check
TCP ClientConfirm network reachability of the device IP, port, and gateway to the device.

Optional data types: Boolean, Byte, Int16, UInt16, Int32, UInt32, Int64, UInt64, Float, Double, String, Decimal

This list describes types allowed by the plugin editor. Address width, arrays, string length and read/write restrictions still follow this page; it does not mean that every address supports every type.

Plugin properties

Protocol parameters

SettingDescription
Network numberDefault: 0; fill in: text input. Network number; the network number used by MC 3E routing
PLC numberDefault: 255; fill in: text input. PLC number; target PLC number, default 0xFF
Module IO numberDefault: 1023; fill in: text input. Module IO number; target module IO number, default 0x03FF
Module station numberDefault: 0; fill in: text input. Module station number; target module station number

Address rules

AreaNumbering and unitAddress example
X / Y / L / RBits, decimal WORD.hexadecimal bitR10.A
TS / CS / SMBits, decimal numbersTS10
DT / LD / TN / CN / SDWORD, decimal numbersDT100

Boolean access inside a WORD requires .0–.15. Only TCP Client is supported; implicit aliases such as D90000/R900.0 are not provided.

Device debug

Enter “Development Configuration → Collection Configuration”, select the current device then open “Protocol Debug” at the top of the workspace.

PanasonicMcMaster: Read/Write

PanasonicMcMaster: Messages

Functions

FunctionPurpose
Read and writeRead a confirmed point and write only to an approved test point.
MessagesView sent and received frames, protocol fields, and error details.

Verify the configuration

Monitor DT100 online in the Panasonic engineering tool, compare the gateway value and confirm a new sample.

Troubleshooting

  • DT/LD WORD areas are decimal; X/Y/L/R use decimal WORD.hexadecimal bit. This driver supports only TcpClient and does not use Mitsubishi D/M addresses.