On this page
Panasonic MC 3E Binary master
Panasonic QnA compatible MC 3E PLC address read and write driver
Open the plugin
Enter “Development Configuration → Collection Configuration”, create a device and select “PanasonicMcMaster” in “Collection Plugin”.
Supported channels and data types
| Channel type | Pre-configuration check |
|---|---|
| TCP Client | Confirm network reachability of the device IP, port, and gateway to the device. |
Optional data types: Boolean, Byte, Int16, UInt16, Int32, UInt32, Int64, UInt64, Float, Double, String, Decimal
This list describes types allowed by the plugin editor. Address width, arrays, string length and read/write restrictions still follow this page; it does not mean that every address supports every type.
Plugin properties
Protocol parameters
| Setting | Description |
|---|---|
| Network number | Default: 0; fill in: text input. Network number; the network number used by MC 3E routing |
| PLC number | Default: 255; fill in: text input. PLC number; target PLC number, default 0xFF |
| Module IO number | Default: 1023; fill in: text input. Module IO number; target module IO number, default 0x03FF |
| Module station number | Default: 0; fill in: text input. Module station number; target module station number |
Address rules
| Area | Numbering and unit | Address example |
|---|---|---|
X / Y / L / R | Bits, decimal WORD.hexadecimal bit | R10.A |
TS / CS / SM | Bits, decimal numbers | TS10 |
DT / LD / TN / CN / SD | WORD, decimal numbers | DT100 |
Boolean access inside a WORD requires .0–.15. Only TCP Client is supported; implicit aliases such as D90000/R900.0 are not provided.
Device debug
Enter “Development Configuration → Collection Configuration”, select the current device then open “Protocol Debug” at the top of the workspace.


Functions
| Function | Purpose |
|---|---|
| Read and write | Read a confirmed point and write only to an approved test point. |
| Messages | View sent and received frames, protocol fields, and error details. |
Verify the configuration
Monitor DT100 online in the Panasonic engineering tool, compare the gateway value and confirm a new sample.
Troubleshooting
- DT/LD WORD areas are decimal; X/Y/L/R use decimal WORD.hexadecimal bit. This driver supports only TcpClient and does not use Mitsubishi D/M addresses.
Related links
- Collection configuration: View channel, device and common variable configuration.
- Plugin Index: Find other collection or data-forward plugins.