CJ/T 188 meters

CJ/T 188 Urban construction industry measurement protocol collection driver

Open the plugin

Enter “Development Configuration → Collection Configuration”, create a device and select “CJ/T 188” in “Collection Plugin”.

Supported channels and data types

Channel typePre-configuration check
TCP ClientConfirm network reachability of the device IP, port, and gateway to the device.
TCP serverConfirm that the local listening address and port are available, and allow on-site devices to actively connect to the gateway.
Serial PortConfirm that the serial port is not occupied by other programs and maintains the same baud rate, data bits, stop bits and parity bits as the device.

Optional data types: Boolean, Byte, Int16, UInt16, Int32, UInt32, Int64, UInt64, Float, Double, String, Decimal

This list describes types allowed by the plugin editor. Address width, arrays, string length and read/write restrictions still follow this page; it does not mean that every address supports every type.

Plugin properties

Protocol parameters

SettingDescription
Default addressDefault: 00000000000001; fill in: text input. Set the default station number used when the station number is not specified separately in the variable address.
Instrument typeDefault: 16; fill in: text input. Set the instrument type used for protocol communication.
Enable leading charactersDefault: Yes; fill in: switch. Controls whether the “Enable Leader” feature is enabled.
Match response addressDefault: Yes; fill in: switch. Controls whether the “match response address” feature is enabled.

Connection configuration

SettingDescription
DTU IDFill in: text input. Sets the identifier used to identify the current device connection through the DTU service.

Address rules

  • Data identification uses two or three bytes, for example 90-1F; available s = fourteen-digit address field; prefix specifies the instrument.

Device debug

Enter “Development Configuration → Collection Configuration”, select the current device then open “Protocol Debug” at the top of the workspace.

CJ/T 188: Read/Write

CJ/T 188: Messages

Functions

FunctionPurpose
Read and writeRead a confirmed point and write only to an approved test point.
MessagesView sent and received frames, protocol fields, and error details.

Verify the configuration

Read the same data identifier with an instrument tool and compare the decoded BCD value and unit multiplier; the first byte alone is not the accumulated quantity.

Troubleshooting

  • The address field has 14 digits, unlike DL/T 645. The data identifier and meter type must come from the same device protocol table.
  • The serial port device does not respond: Confirm that the serial port is not occupied, and check the baud rate, data bits, stop bits and parity bits.