Allen-Bradley PCCC master

Allen-Bradley PCCC file table address read and write driver

Open the plugin

Enter “Development Configuration → Collection Configuration”, create a device and select “PCCCMaster” in “Collection Plugin”.

Supported channels and data types

Channel typePre-configuration check
TCP ClientConfirm network reachability of the device IP, port, and gateway to the device.

Optional data types: Boolean, Byte, Int16, UInt16, Int32, UInt32, Int64, UInt64, Float, Double, String, Decimal

This list describes types allowed by the plugin editor. Address width, arrays, string length and read/write restrictions still follow this page; it does not mean that every address supports every type.

Plugin properties

Protocol parameters

SettingDescription
Target slotDefault: 0; fill in: text input. Set the slot number where the PLC CPU module is located.
Backplane portDefault: 1; fill in: text input. Set up a controller backplane port or path segment.

Address rules

File type code (decimal)File typeAddress formatExample
130OutputO{file}:{element}O1:10
131InputI{file}:{element}I2:20
132StatusS{file}:{element}S3:30
133BitB{file}:{element}B4:40
134TimerT{file}:{element}T5:50
135CounterC{file}:{element}C6:60
136ControlR{file}:{element}R7:70
137IntegerN{file}:{element}N8:80
138Floating pointF{file}:{element}F9:90
141StringST{file}:{element}ST10:100
142ASCIIA{file}:{element}A11:110
145Long integerL{file}:{element}L12:120

The file and element must exist in the controller; these examples explain syntax and do not create files. N7:0 is element 0 of integer file 7, rather than a CIP tag name. For bit access, also supply the bit index from the point list.

Device debug

Enter “Development Configuration → Collection Configuration”, select the current device then open “Protocol Debug” at the top of the workspace.

Read and write

PCCCMaster: Read/Write

Perform read or write verification according to the current plugin address rules; confirm on-site security and permissions before writing.

Messages

PCCCMaster: Messages

Check the device’s message sending and receiving and protocol logs to locate message format, connection and parsing problems.

Functions

FunctionPurpose
Read and writeRead a confirmed point and write only to an approved test point.
MessagesView sent and received frames, protocol fields, and error details.

Verify the configuration

Monitor N7:0 online in the PLC engineering tool, compare its value with the gateway variable and confirm advancing sample times.

Troubleshooting

  • File-table syntax is area+file:element rather than a CIP tag name; check file type, element width and target route.