Skip to Content
On this page

GE SRTP master

GE SRTP PLC address reading and writing, status and clock diagnostic driver

Open the plugin

Enter “Development Configuration → Collection Configuration”, create a device and select “GeSrtpMaster” in “Collection Plugin”.

Supported channels and data types

Channel typePre-configuration check
TCP ClientConfirm network reachability of the device IP, port, and gateway to the device.

Optional data types: Boolean, Byte, Int16, UInt16, Int32, UInt32, Int64, UInt64, Float, Double, String

This list describes types allowed by the plugin editor. Address width, arrays, string length and read/write restrictions still follow this page; it does not mean that every address supports every type.

Address rules

  • GE SRTP addresses start with 1.
  • I, Q, M, T, SA, SB, SC, S, G support boolean and raw byte access, such as M1, Q100.
  • AI, AQ, R use sixteen-digit WORD access, such as R1, AI100, and do not support Boolean bit access.
  • The default TCP port of PLC is 18245; the initialization exchange will be re-executed every time TCP reconnects.

Special methods

MethodPurposeParameters
ReadClockAsyncRead PLC clockNo parameters
ReadProgramNameAsyncRead program nameNo parameters

Device debug

Enter “Development Configuration → Collection Configuration”, select the current device then open “Protocol Debug” at the top of the workspace.

Dedicated debugging page

The protocol debugging page is used to read the device status and register data of GE SRTP.

GeSrtpMaster: Operations

Debugging notes

The dedicated page verification can be completed by reading the PLC clock and current program name. There is no writing operation on this page.

Functions

FunctionPurpose
Read PLC clockUse Read PLC clock to inspect mapped values, status, counters, recent messages, or the latest result.
Read program namesUse Read program names to inspect mapped values, status, counters, recent messages, or the latest result.

Verify the configuration

Monitor R1 online in the PLC engineering tool, compare its value with the gateway variable and confirm advancing sample times.

Writes and control operations require an approved test point and the site safety procedure.

Troubleshooting

  • R/AI/AQ do not support Boolean bit access. Initialization runs on each reconnect; check it before diagnosing addresses.
  • Special method execution fails: Check method parameters and permissions; control, write or reset methods also need to confirm that the device is in a state that allows operation.